CSJ 20 Series

Cold Shrink Cable Joints for 1/C, 5 – 15 kV XLPE and EPR extruded dielectric metal tape, wire shielded power cables for the electrical construction markets.

Features and Benefits

  • Versatile, Cold Shrink design
  • Quick and Easy installation
  • Accommodates a wide range of conductor sizes
  • Geometric stress cone & stress controlling sealant
  • Spiral ripcord housing
  • Cold shrink jacketing tube
  • Compact design for all types of extruded dielectric cables covering the full range from #4 AWG to 1000 kcmil
  • One piece joint designed for quick, easy and cost effective installation
  • Provides exceptional performance & secondary seal
  • Demonstrates superior cable sealing & voltage withstand characteristics per electrical utility industry standards
  • Designed for use with in-line compression connector
  • Tough rubber outer covering protects against damage from improper backfill

Standards

  • Rated to IEEE-404-2000

Test Reports

  • The CSJ Series Joints were tested to the requirements of IEEE-404-2000 at an independent laboratory.
  • Test report available: HVS.290310

Market/Applications

  • Transit
  • Water/Waste Water Treatment
  • Shipboard
  • OEM
  • Transit
  • Communication Power & Control
  • Power Distribution
  • Industrial Construction/Automation
  • Civil Construction Projects
  • Industrial
  • Communications Cable Splice & Protection
  • Petrochem/Pulp & Paper
  • Power Distribution – MV
  • Utility
  • Commercial Construction Projects
  • Mining

Ordering

  • Find the cables voltage class and conductor size(s) to be spliced. Select the kit order number that covers the conductor size range and cable insulation O.D. range.
  • Confirm the dimensional data particularly when the conductor size range is at the extremes of the range. The overlap in size range allows for size transitions when splicing different cable sizes. The determining factors for selection are that the dimension ranges for the primary insulation and connector dimensions are met and the jacket diameter maximums are not exceeded.
  • A cable preparation/cleaning kit can be included with the kit by adding the suffix to the end of the order number.
Order NumberConductor Size RangeInsulation O.D. RangeJacket O.D. MaximumConnector DimensionsNominal Kit Installed Length
Maximum O.D.Maximum Length
inmminmminmminmminmm
5 kV (90-110 mils)
CSJ 820#4 – #2/0 AWG0.51-0.6413-16.20.91230.51133.158018455
CSJ 821#2/0 – 250 kcmil0.64-0.7916.2-20.21.10280.6416.23.158018455
CSJ 822250 – 500 kcmil0.79-1.0420-26.41.42360.79203.9510018455
CSJ 823500 – 1000 kcmil1.02-1.4526-36.81.77451.02265.5014020505
8 kV (115 mils)
CSJ 820#4 – #1/0 AWG0.51-0.6413-16.20.91230.51133.158018455
CSJ 821#1/0 – #4/00.64-0.7916.2-20.21.10280.6416.23.158018455
CSJ 822#4/0 – 500 kcmil0.79-1.0420-26.41.42360.79203.9510018455
CSJ 823500 – 1000 kcmil1.02-1.4526-36.81.77451.02265.5014020505
15kV (175-220 mils)
CSJ 1520#20.51-0.6413-16.20.91230.51133.158018455
CSJ 1521#2 – #1/00.64-0.7916.2-20.21.10280.6416.23.158018455
CSJ 1522#1/0 -350 kcmil0.79-1.0420-26.41.42360.79203.9510018455
CSJ 1523350 – 750 kcmil1.02-1.4526-36.81.77451.02265.5014020505