CT G Series

Heat shrink cable terminations for single core, 5 kV to 35 kV, copper tape, drain wire, UniShield or lead sheathed XLPE and EPR power cables for the electrical construction market.

Features and Benefits

  • Fast, consistent installation means lower installed costs
  • Heat activated seals ensure maximum protection against moisture ingress
  • Installation environment: use of torch adds flexibility to cable preparation in any climate
  • Light weight construction requires no additional support
  • UV resistant, non-tracking outer tube for long life, even under adverse conditions
  • Slim profile allows installation in confined switch gear cubicles

Standards

  • Rated to IEEE 48-1996, Class 1

Test Reports

The CT 080 series through CT 350 series terminations were tested to the requirements of IEEE 48-1996 Class 1 at an independent laboratory.

Test reports are available as follows:

  • CT 080 series: HVS020075
  • CT 150 series: HVS 020076
  • CT 250 series: HVS020077 and HVS020083
  • CT 350 series: HVS020078

Market/Applications

  • Transit
  • Water/Waste Water Treatment
  • Shipboard
  • OEM
  • Communication Power & Control
  • Power Distribution
  • Civil Construction Projects
  • Industrial
  • Petrochem/Pulp & Paper
  • Power Distribution – MV
  • Utility
  • Commercial Construction Projects
  • Mining

Note: Termination Tests to IEEE 48-1996 Standard Test Procedures and Requirements for Alternating Current Cable Terminations 2.5 kV through 765 kV

Ordering

  • Select the termination kit size for the copper tape, drain wire, lead sheathed or UniShield shielded power cable to be terminated.
  • Confirm the cable dimensions. At the high end of the conductor range it may be necessary to select the next larger size kit. Dimensions are based on cable information from AEIC CS5 and CS6 cable standards.
  • For terminations that will be exposed to direct precipitation select the outdoor termination by adding the suffix to the order number. To add an external grounding kit for tape shielded cables add to the order number. To include a cable preparation kit add the suffix to the end of the order number.
    FOR EXAMPLE: a 15 kV outdoor termination for 2/0 cable with an external ground kit and cable preparation kit would be CT 151EGP.
Indoor Kit
Order Number
Outdoor Kit
Order Number
Conductor Size RangeInsulation Diameter
Min – Max
Jacket Diameter
Max
inmminmm
5 kV
CT 081(G)CT 081E(G)#4 – #1 AWG0.40 – 0.6011 – 160.9524
CT 082(G)CT 082E(G)1/0 – 250 kcmil0.60 – 0.9516 – 241.2030
CT 083(G)CT 083E(G)300 – 500 kcmil0.80 – 1.2521 – 351.5038
CT 084(G)CT 084E(G)600 – 1750 kcmil1.10 – 1.7528 – 452.1055
CT 085(G)CT 085E(G)1500 – 2500 kcmil1.60 – 2.4541 – 622.7570
8 kV
CT 081(G)CT 081E(G)#6 – #2 AWG0.40 – 0.6011 – 160.9524
CT 082(G)CT 082E(G)#1 – 4/0 AWG0.60 – 0.9516 – 241.2030
CT 083(G)CT 083E(G)250 – 500 kcmil0.80 – 1.2521 – 351.5038
CT 084(G)CT 084E(G)600 – 1750 kcmil1.10 – 1.7528 – 452.1055
CT 085(G)CT 085E(G)1500 – 2500 kcmil1.60 – 2.4541 – 622.7570
15 kV
CT 151(G)CT 151E(G)#4 – 4/0 AWG0.60 – 1.0516 – 271.4537
CT 152(G)CT 152E(G)3/0 – 350 kcmil0.80 – 1.2521 – 351.7545
CT 153(G)CT 153E(G)400 – 1000 kcmil1.10 – 1.6528 – 422.1055
CT 154(G)CT 154E(G)1250 – 2500 kcmil1.60 – 2.4541 – 632.7570
25 – 28 kV
CT 251(G)CT 251E(G)#2 – 350 kcmil0.80 – 1.4021 – 351.8046
CT 252(G)CT 252E(G)350 – 1000 kcmil1.10 – 1.8028 – 462.5064
CT 253(G)CT 253E(G)1000 – 1750 kcmil1.60 – 2.4541 – 632.7570
35 kV
CT 351(G)CT 351E(G)#1 – 250 kcmil0.95 – 1.4024 – 351.9048
CT 352(G)CT 352E(G)250 – 1000 kcmil1.25 – 2.1032 – 532.6066